a. 60 digit phone numbers --- for all 8 phone numbers.
b.
Telephone line fault detection --- tests phone line at regular programmed intervals
and flashes LED on dialer front panel upon failure.
c.
Automatic selection of pulse versus tone dialing --- tests for capability upon power up
without user intervention and maybe overridden for non-standard PBX systems.
d.
Call progress monitoring (CPM) --- detects busy and ringing signals; waits until phone
is answer to annunciate voice alarm; abandons call if line is busy or no answer and
quickly tries next number.
e.
Numeric pager support --- allows pause characters and pager system terminator
characters such as # or *.
f.
PBX support --- ignores non-standard dialing tones and allows pause characters to
allow waiting for outside line.
1.2
Programming Parameters and Other Features
Dialer shall be programmed using a standard touch tone telephone handset that shall be
connected to the dialers through the RJ11 programming port. After programming, the
programming telephone shall be disconnected and removed from the dialer. Pre-programmed
speech shall provide entry guidance and confirmation of programmable features. Coded
programming using function codes shall provide direct access to specific programmable items.
The following parameters/features shall be available. When software based, parameters shall be
alterable from their default values through the local programming telephone handset:
a.
Messages --- voice alarm messages for each alarm channel and for dialer station
identification shall be digitally recorded at high resolution. Permanently stored factory
recorded messages shall be included as default alarm messages and default station
identification so as to allow the dialer to be fully functional even with no user recorded
messages. Permanent messages to support user programming shall be provided.
b.
Alarm Trip Delay --- each alarm channel response time shall be individually
programmable from 0.1 to 999.9 seconds. Default shall be 2.0 seconds. Main power
loss response time shall be fixed at 5 minutes.
c.
Delay Between Alarm Dial Outs --- shall be programmable from 0.1 to 99.9 minutes.
Default shall be 2.0 minutes.
d.
Alarm Reset Time --- shall be programmable from 0.1 to 99.9 hours. Default shall be
1.0 hour.
e.
Incoming Ring Response (dialer answer) Delay --- shall be programmable from 1 to
20 rings. Default shall be 1 ring.
f.
Alarm Message Repetitions --- shall be fixed at 5 repetitions.
g.
Station Identification --- see “a. Messages” above.
h.
Input Alarm Criteria --- each dry-contact alarm input channel shall be independently
programmable for non-alarm OPEN or CLOSED circuit. Alarm will occur when dry
contacts transition from non-alarm state.
i.
Built-In Microphone --- shall monitor background sounds at site whenever user is in
phone contract with dialer.
j.
Local Alarm Output --- transistor output for TTL or relay drive500 MA, 24 VDC max)
activated during unacknowledged alarm.
k. Arming of System --- front panel shall have an OFF/ARMED/DISARMED switch.
l.
Phone Dialing Mode --- shall be programmable for automatic, pulse, or touch tone.
Default shall be automatic mode.
m.
Phone Numbers --- up to eight phone number shall be programmable. Each phone
number shall be up to 60 characters long. Pauses, *, and # characters shall be
supported for numeric pager communications.
n.
Metal Enclosure --- shall be NEMA-12 and shall be capable of surface or flush mount.
Enclosure shall have LED lights indicating main power failure, DISARMED status,